Medium Voltage antenne bondele kabels wurde benammen brûkt foarsekundêre overhead linenop peallen of as feeders nei wenromte.
Medium Voltage antenne bondele kabels wurde benammen brûkt foarsekundêre overhead linenop peallen of as feeders nei wenromte.
TS EN 60502-2 Stromkabels mei ekstruderde isolaasje en har aksessoires foar nominale spanningen fan 1 kV (Um = 1.2 kV) oant 30 kV (Um = 36 kV) - Diel 2: Kabels foar nominale spanningen fan 6 kV ( Um = 7,2 kV) oant 30 kV (Um = 36 kV)
6.35/11kV, 19/33kV
Fase Conductor: Klasse 2 Circular kompakte strâne aluminium
Dirigint Skerm: Extruded semi-conductive laach
Isolaasje: XLPE (Cross-linked polyetyleen)
Isolaasje skerm: Extruded semi-conductive laach
Metallic skerm: Koper tried skerm as koperen tape skerm
Separator: Semi-conductive swelbere tape
Bûtenmantel: HDPE (polyetyleen mei hege tichtheid)
Support Dirigent:Galvanized stielen triedden
Isolearre kearn: reade, giele en blauwe kearnmarkearringsband
Outed skede: Swart
Operating Temperatuer: 90 ° C XLPE
Temperaturberik: -20 ° C PE sheath
Koarte circuit temperatuer (5 sekonden maksimum doer): 250 ° C XLPE
Bending Radius: 15 x totale diameter
Wy produsearje kwaliteitskabels mei heechweardich materiaal:
Ryk ûnderfining team wit wat jo fraach is:
Plant mei goede foarsjenningen en kapasiteit om op-tiid levering te garandearjen:
Oantal kearnen x Nominale Cross Section | Fase Conductor | Messenger Suspension Unit | Trochrinnende hjoeddeistige wurdearring by 300 ° C Ambient Temp. | ||||
Stranding | Nominaal Sectional Area | Maksimum Conductor Resistance | Stranding | Nominaal Sectional Area | Breaking Load | ||
No.×mm² | Nee × mm | mm² | Ω/Km | Nee × mm | mm² | kN | A |
3X50 + 1X25 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 116 |
3X70 + 1X50 | 19/.14 | 70 | 0.443 | 7/3.15 | 50 | 62 | 210 |
3X95+ 1X50 | 19/2.52 | 95 | 0.32 | 7/3.0 | 50 | 60 | 173 |
3X185+1X120 | 37/2.52 | 185 | 0.164 | 7/4.67 | 120 | 150 | 259 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 365 |
3X240 +1X50 | 61/2.25 | 240 | 0.125 | 7/3.15 | 50 | 62 | 500 |
Oantal kearnen x Nominale Cross Section | Fase Conductor | Messenger Suspension Unit | Trochrinnende hjoeddeistige wurdearring by 300 ° C ambient temp | ||||
Stranding | Nominaal Sectional Area | Maksimum Conductor Resistance | Stranding | Nominaal Sectional Area | Breaking Load | ||
No.×mm² | Nee × mm | mm² | Ω/Km | Nee × mm | mm² | kN | A |
3X50 + 1X50 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 165 |
3X150+ 1X50 | 37/2.25 | 150 | 0.206 | 7/3.0 | 50 | 60 | 315 |
3X185+1X70 | 37/2.52 | 185 | 0.164 | 7/3.57 | 70 | 91 | 355 |
3X70 +1X50 | 19/2.14 | 7 | 0.443 | 7/3.15 | 50 | 62 | 250 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 370 |